© 2008 Schneider Electric
Parameter
● Operating modes
The operating mode in which this block operates is
specified in the application software for each block
(movement blocks 1 - 5). The following operating
modes are available:
– Normal operation
– Master mode
– Slave mode
– Monitoring mode
Depending on the operating mode different
parameters and communication objects will be
displayed. Each operating mode can operate
brightness-dependently or non-brightness-
dependently.
Normal operation
In this operating mode the movement detector does
not have any external trigger objects (master trigger
object, trigger object). Telegrams cannot be sent
cyclically and this means a master-slave system
cannot be set up. In the default setting, the movement
detector transmits an ON telegram at the start of
movement and transmits an OFF telegram when the
movement time (staircase timer) has expired.
|
Note:
Use the "Normal operation" setting when the
movement detector is working for itself alone.
In other words, one movement detector is used
for each room and it switches one light or one
light panel.
Master mode
With master mode all of the possible parameters and
communication objects of the movement detector are
available. A master-slave system can be set up with
the aid of the master trigger object or the trigger
object. In the default setting, the movement detector
transmits an ON telegram at the start of movement
and transmits an OFF telegram when the movement
time (staircase timer) has expired.
Slave mode
In slave mode the default setting is that ON telegrams
are sent cyclically when a movement is detected.
These telegrams are intended for the master trigger
object or for the trigger object of the master.
Monitoring mode
In monitoring mode the default setting is that ON
telegrams are sent cyclically when a movement is
detected. At the end of the movement time (cycle
time with movement) OFF telegrams are transmitted
cyclically.
|
Note:
Use the "Monitoring mode" setting when the
movementmovement detector is being used for
room monitoring and telegrams are to be sent
cyclically on the bus.
Block X, general brightness
Parameter Setting
Movement detection is brightness-dependent
independent of brightness
Brightness threshold adjustable
via
Parameters
Potentiometer
Overwrite brightness threshold
during download
Enabled
Disabled
Brightness threshold (3 - 1000 lux)
see "General" tab
3 - 1000 lux; preconfiguration:
130
Brightness threshold object Disabled
Enabled
Brightness object 1 bit Do not send
Tr a ns mi t
Transmit inverted
Always-dark object (= not
brightness-dependent)
Disabled
Enabled
Switch on at movment Enabled
Disabled